Summary
CVE-2026-102073 is an integer underflow (CWE-191) vulnerability in the web service of several Siemens APOGEE and TALON TC building automation controllers. An unauthenticated remote attacker can exploit it to read portions of device memory or cause a denial-of-service condition. It is rated High (CVSS v3.1 8.2).
Technical details
- Root cause: The web service does not properly validate the length of user-controllable input (CWE-191, Integer Underflow / Wrap or Wraparound).
- Trigger conditions: The device’s web service must be enabled. Siemens notes the FTP/Web service is disabled by default.
- Attack vector: Network; no authentication or user interaction required, low attack complexity.
- Impact: Disclosure of portions of device memory (high confidentiality impact) and denial of service (low availability impact).
Affected software
- APOGEE PXC Compact and PXC Modular (BACnet): all versions before V3.5.7
- APOGEE PXC Compact and PXC Modular (P2 Ethernet): all versions before V2.8.21
- TALON TC Compact and TALON TC Modular (BACnet): all versions before V3.5.7
- APOGEE MBC (PPC) and MEC (PPC), BACnet and P2 Ethernet variants: all versions (no fix available per Siemens)
- Siemens also lists Desigo PXC series and Desigo PXM20-E (all versions ≥V2.3) as having no fix in the same advisory.
Severity
- CVSS v3.1 base score: 8.2 (High)
- Vector:
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:L - CVSS v4.0: 8.8 (
CVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:H/VI:N/VA:L/SC:N/SI:N/SA:N)
Mitigation and recommended actions
- Immediate: Update APOGEE PXC Compact/Modular (BACnet) and TALON TC Compact/Modular (BACnet) to V3.5.7 or later. Update APOGEE PXC Compact/Modular (P2 Ethernet) to V2.8.21 or later.
- No patch available (APOGEE MBC/MEC, all versions): Apply Siemens’ workaround and disable the FTP/Web service (disabled by default). Verify that it is not enabled.
- Review Siemens advisory SSA-333035 for the full list of affected products and guidance.