Summary
CVE-2026-12655 is an authentication bypass vulnerability (CWE-294, Authentication Bypass by Capture-replay) in the Rockwell Automation 1732E ArmorBlock® I/O modules. An unauthenticated network attacker can change the device’s webserver password without valid credentials, which can lead to admin account compromise. Rockwell rates it High severity (CVSS v4.0 8.8).
Technical details
- Root cause: Authentication bypass by capture-replay (CWE-294) in the device’s webserver password handling.
- Trigger conditions: No authentication, privileges or user interaction are required. Attack complexity is low.
- Attack vector: Network.
- Impact: An attacker can modify the webserver password, take over the admin account, and make unauthorized configuration changes. The CVSS v4.0 vector rates the impact as high on integrity and availability of the vulnerable system.
- The same advisory also covers CVE-2026-12656, a separate denial-of-service issue.
Affected software
- Rockwell Automation 1732E ArmorBlock® I/O: software versions 3.012 and earlier (listed in the CVE record as 0 through 3.012).
- Rockwell’s advisory lists multiple catalog numbers, including 1732E-IB16M12R, 1732E-OB16M12R and 1732E-16CFGM12R, among others. See the advisory for the full list.
Severity
- CVSS v4.0: 8.8 (High),
CVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:N/VI:H/VA:H/SC:N/SI:N/SA:N - CVSS v3.1: Rockwell’s advisory lists a base score of 9.1. A vector string was not available from the sources reviewed.
Mitigation and recommended actions
- Immediate: Upgrade to software version 3.013 or later, which corrects the vulnerability.
- If you cannot upgrade immediately: Rockwell documents no workarounds. It recommends applying its security best practices. These include restricting network access to the devices and not exposing them to the internet. For help, contact Rockwell TechConnect or [email protected].